GUNDREMMINGEN
In Gundremmingen ging 1966 einer der ersten kommerziell betriebenen deutschen Großreaktoren ans Netz. Block A wurde nach einem Störfall 1977 endgültig abgeschaltet; da waren die erheblich größeren Nachfolger B und C bereits im Bau. Die beiden Kühltürme der Doppelblockanlage wurden 2025 gesprengt, der Rückbau dauert an.
One of Germany's first commercially operated large nuclear reactors was connected to the grid at Gundremmingen in 1966. Unit A was permanently shut down after an incident in 1977, by which time the much larger successor units B and C were already under construction. The two cooling towers of the twin-unit station were demolished by controlled blasting in 2025; dismantling continues.
Anlagen am Standort:Facilities at the site:
- Brennelemente-Zwischenlager Gundremmingen (BZM)
- Kernkraftwerk Gundremmingen A
- Kernkraftwerk Gundremmingen B
- Kernkraftwerk Gundremmingen C
- Gundremmingen spent fuel interim storage facility (BZM)
- Gundremmingen A
- Gundremmingen Nuclear Power Plant, Unit B
- Gundremmingen Nuclear Power Plant, Unit C
Standortgeschichte
Der Kraftwerksstandort entstand an der Donau im Landkreis Günzburg. Vor der Entscheidung für Gundremmingen waren andere Donauabschnitte in Betracht gekommen, darunter Bertoldsheim; Bedenken wegen des Trinkwasserschutzes beeinflussten die Standortsuche. Getragen wurde die Betreibergesellschaft von RWE (75 Prozent) und Bayernwerk (25 Prozent); der Minderheitsanteil lag später bei E.ON beziehungsweise PreussenElektra. Block A lieferte seit 1966 Strom. 1975 starben bei einem Arbeitsunfall zwei Beschäftigte durch austretenden heißen Dampf. Nach einem schweren Störfall im Januar 1977 wurde der Reaktor nicht wieder in Betrieb genommen.
Noch während Block A lief, begann im Juli 1976 unmittelbar daneben der Bau von Gundremmingen B und C. Die beiden Siedewasserreaktoren der KWU-Baulinie 72 hatten zusammen 2.688 Megawatt elektrische Bruttoleistung und bildeten die leistungsstärkste Kernkraftwerks-Doppelblockanlage Deutschlands. Block B speiste im März 1984 erstmals Strom ins Netz, Block C im November desselben Jahres. Für beide Reaktoren war auch der Einsatz von Mischoxid-Brennelementen genehmigt.
Heute finden auf dem Gelände Rückbau und Abfallbehandlung statt. Im ehemaligen Maschinenhaus von Block A ist eine Rückbaufabrik eingerichtet; das Brennelemente-Zwischenlager wird gesondert betrieben. Die beiden 160 Meter hohen Kühltürme von B und C wurden am 25. Oktober 2025 gesprengt.
Standortdaten: Gundremmingen, Landkreis Günzburg, Bayern · Block A: Stromerzeugung 1966–1977 · Block B: Stromerzeugung 1984–2017 · Block C: Stromerzeugung 1984–2021 · Doppelblockanlage 2 × 1.344 MW brutto · Standortzwischenlager seit 2006 · Kühltürme abgebrochen 25.10.2025
History of the site
The power station site was developed on the Danube in the Günzburg district. Other stretches of the river, including Bertoldsheim, had been considered before Gundremmingen was selected; concerns about drinking-water protection influenced the choice. The operating company was owned by RWE (75 per cent) and Bayernwerk (25 per cent); the minority shareholding later passed to E.ON and then PreussenElektra. Unit A generated electricity from 1966. In 1975, two workers died in an industrial accident involving escaping hot steam. Following a serious incident in January 1977, the reactor was not restarted.
Construction of Gundremmingen B and C began immediately alongside Unit A in July 1976, while it was still operating. Together the two boiling water reactors of KWU's Generation 72 design had a gross electrical output of 2,688 megawatts, making them Germany's most powerful twin-unit nuclear power station. Unit B first supplied electricity to the grid in March 1984 and Unit C in November of the same year. Both reactors were also licensed to use mixed-oxide fuel elements.
Dismantling and waste treatment now take place on the site. A dismantling facility has been established in Unit A's former turbine hall; the spent fuel interim storage facility is operated separately. The two 160-metre-high cooling towers of units B and C were demolished by controlled blasting on 25 October 2025.
Site data: Gundremmingen, Günzburg district, Bavaria · Unit A: electricity generation 1966–1977 · Unit B: electricity generation 1984–2017 · Unit C: electricity generation 1984–2021 · Twin-unit station 2 × 1,344 MW gross · On-site interim storage facility since 2006 · Cooling towers demolished 25 October 2025
Am Standort:At the site:
- Lagertyp
- Brennelemente-Zwischenlager
- Betreiber
- BGZ
- Inbetriebnahme
- 2006
- Genehmigte Kapazität
- 192 Stellplätze · 1.850 t Schwermetall
- Aufbewahrung genehmigt bis
- 2046
- Status
- in Betrieb
Am Standort:At the site:
- Storage type
- Spent fuel interim storage facility
- Operator
- BGZ
- Commissioned
- 2006
- Licensed capacity
- 192 storage positions · 1,850 tonnes of heavy metal
- Storage authorised until
- 2046
- Status
- in operation
Glossar:Glossary:
CASTOR-Behälter
Transport- und Lagerbehälter für abgebrannte Brennelemente und hochradioaktive Abfälle aus der Wiederaufarbeitung. CASTOR steht für Cask for Storage and Transport of Radioactive Material und ist ein Markenname der Gesellschaft für Nuklear-Service (GNS).
Viele CASTOR-Bauarten besitzen einen massiven Körper aus Gusseisen mit Kugelgraphit, mit mehrere Dezimeter starken Wänden. Der Behälter schirmt Strahlung ab, schließt radioaktive Stoffe ein und gibt ihre Zerfallswärme an die Umgebung ab. Bei der Zwischenlagerung wird in der Regel ein Doppeldeckel-Dichtsystem eingesetzt. Der Raum zwischen den Deckeln steht unter Druck und wird auf Dichtheit überwacht. Je nach Inhalt und Reaktortyp unterscheiden sich Größe und Ausführung der Behälter erheblich.
Umgangssprachlich wird CASTOR häufig auch für andere Behälter mit hochradioaktivem Inhalt verwendet. Vergleichbare Transport- und Lagerbehälter gibt es jedoch auch unter anderen Produktbezeichnungen.
Glossar:Glossary:
CASTOR Cask
A transport and storage cask for spent nuclear fuel and high-level radioactive waste from reprocessing. CASTOR stands for Cask for Storage and Transport of Radioactive Material and is a trade name belonging to Gesellschaft für Nuklear-Service (GNS).
Many CASTOR models have a massive body made of ductile cast iron, with walls several tens of centimetres thick. The cask shields radiation, contains radioactive substances and dissipates their decay heat to the surroundings. During interim storage, a double-lid sealing system is generally used. The space between the lids is pressurised and monitored for leakage. Cask dimensions and configurations vary considerably according to the contents and reactor type.
In everyday German usage, CASTOR is often also used to refer to other casks containing high-level radioactive material. Comparable transport and storage casks are, however, sold under other product names as well.
Gundremmingen A war nach dem Versuchsatomkraftwerk Kahl der nächste große Schritt der Zusammenarbeit von AEG und General Electric. RWE und Bayernwerk gaben 1962 den Auftrag für einen Siedewasserreaktor mit 250 Megawatt elektrischer Bruttoleistung. Das Projekt wurde erheblich öffentlich gefördert und gegen Betriebsrisiken abgesichert. Bei der Errichtung verzögerten Probleme mit Schweißnähten am Sicherheitsbehälter und Reaktordruckbehälter sowie mit neu konstruierten Umwälzpumpen die Fertigstellung.
Am 14. August 1966 erreichte der Reaktor die erste Kritikalität und am 1. Dezember 1966 den Netzanschluss. Der kommerzielle Betrieb begann am 12. April 1967. Neben der Stromproduktion erprobte der Betreiber Brennelemente, darunter später auch Mischoxidbrennstoff aus Uran und Plutonium. Im November 1975 wurden zwei Arbeiter bei Reparaturen am Primärreinigungssystem von austretendem heißem Dampf tödlich verletzt.
Am 13. Januar 1977 kam es bei Frost und Feuchtigkeit zu Kurzschlüssen auf den Hochspannungsleitungen. Der Reaktor wurde vom Netz getrennt und schnellabgeschaltet. Durch eine Fehlfunktion der Speisewasserregelung gelangte zu viel Wasser in den Reaktor; beim Druckabbau strömte radioaktiv belastetes Wasser in das Reaktorgebäude. Der Wasserstand stieg dort innerhalb weniger Minuten auf mehrere Meter. Die notwendigen Reparaturen und Nachrüstungen erschienen dem Betreiber schließlich wirtschaftlich nicht vertretbar, zumal die Blöcke B und C bereits im Bau waren. 1980 beschloss er die endgültige Aufgabe des Blocks. Die Stilllegungsgenehmigung wurde am 26. Mai 1983 erteilt.
Die reaktortechnischen Teile wurden schrittweise zerlegt. Ein Teil der Gebäude blieb erhalten und wurde zur Behandlung von Rückbaumaterial des Gesamtstandorts umgenutzt.
Gundremmingen A marked the next major step in cooperation between AEG and General Electric after the Kahl experimental nuclear power plant. In 1962, RWE and Bayernwerk placed an order for a boiling water reactor with a gross electrical output of 250 megawatts. The project received substantial public financial support and protection against operating risks. During construction, problems with welds on the containment vessel and reactor pressure vessel, as well as with newly designed recirculation pumps, delayed completion.
The reactor first achieved criticality on 14 August 1966 and was connected to the grid on 1 December 1966. Commercial operation began on 12 April 1967. In addition to generating electricity, the operator tested fuel assemblies, later including mixed-oxide fuel made from uranium and plutonium. In November 1975, two workers suffered fatal injuries from escaping hot steam while carrying out repairs to the primary purification system.
On 13 January 1977, frost and moisture caused short circuits on high-voltage transmission lines. The reactor was disconnected from the grid and automatically shut down. A malfunction in the feedwater control system then caused too much water to enter the reactor; as pressure was released, radioactively contaminated water flowed into the reactor building. Within minutes, the water level there rose to several metres. The operator eventually considered the necessary repairs and upgrades economically unjustifiable, particularly as Units B and C were already under construction. In 1980, it decided to abandon Unit A permanently. The decommissioning licence was issued on 26 May 1983.
The reactor-related components were dismantled in stages. Some buildings were retained and repurposed for treating materials arising from decommissioning work across the site.
- Reaktortyp
- Siedewasserreaktor
- Bauart / Modell
- Erste deutsche SWR-Generation
- Hersteller
- AEG / General Electric
- Betreiber
- Kernkraftwerk RWE-Bayernwerk
- Leistung thermisch
- 801 MW
- Leistung elektrisch
- 250 MW brutto / 237 MW netto
- Erstkritikalität
- 14.8.1966
- Netzanschluss
- 1.12.1966
- Kommerzieller Betrieb
- 12.4.1967
- Abschaltung
- 13.1.1977
- Rückbau
- Stilllegungsgenehmigung 26.5.1983; im Rückbau
- Status
- im Rückbau
- Reactor type
- Boiling water reactor
- Design / model
- First generation of German boiling water reactors
- Manufacturer
- AEG / General Electric
- Operator
- Kernkraftwerk RWE-Bayernwerk
- Thermal power
- 801 MW
- Electrical output
- 250 MW gross / 237 MW net
- First criticality
- 14 August 1966
- Grid connection
- 1 December 1966
- Commercial operation
- 12 April 1967
- Shutdown
- 13 January 1977
- Decommissioning
- Decommissioning licence issued on 26 May 1983; undergoing dismantling
- Status
- Undergoing dismantling
Glossar:Glossary:
Siedewasserreaktor (SWR)
Leichtwasserreaktor, in dem das Kühlwasser bei einem Druck von etwa 70 bar im Reaktorkern selbst siedet. Der entstehende Dampf wird nach der Abscheidung von Wassertröpfchen direkt zur Turbine geleitet. Anders als beim Druckwasserreaktor gibt es keinen getrennten Dampfkreislauf mit Dampferzeugern. Das Wasser dient zugleich als Kühlmittel und Moderator.
Da der Dampf unmittelbar aus dem Reaktor stammt, wird auch das Maschinenhaus in den Strahlenschutz einbezogen. Die Steuerstäbe werden von unten in den Reaktorkern eingefahren.
Die Siedewasserreaktortechnik wurde maßgeblich von General Electric in den USA entwickelt. In der Bundesrepublik baute die AEG auf Grundlage einer GE-Lizenz das Versuchsatomkraftwerk Kahl und später unter anderem Gundremmingen A, Lingen und Würgassen. Unter dem Dach der Kraftwerk Union (KWU), in der AEG und Siemens ab 1969 ihre Kraftwerksgeschäfte zusammenführten, entwickelten sich daraus die Baulinien 69 (unter anderem Brunsbüttel, Isar 1, Philippsburg 1, Krümmel und Zwentendorf) und 72 (Gundremmingen B und C).
Glossar:Glossary:
Boiling Water Reactor (BWR)
A light-water reactor in which the cooling water boils inside the reactor core at a pressure of approximately 70 bar. After water droplets have been separated out, the resulting steam passes directly to the turbine. Unlike a pressurised water reactor, it has no separate steam circuit with steam generators. The water serves as both coolant and moderator.
Because the steam comes directly from the reactor, radiation protection requirements also extend to the turbine building. Control rods are inserted into the reactor core from below.
Boiling water reactor technology was developed principally by General Electric in the United States. In West Germany, AEG built the Kahl experimental nuclear power station under a GE licence and later built Gundremmingen A, Lingen and Würgassen, among others. Within Kraftwerk Union (KWU), into which AEG and Siemens merged their power station businesses from 1969, this led to Design Generations 69 (including Brunsbüttel, Isar 1, Philippsburg 1, Krümmel and Zwentendorf) and 72 (Gundremmingen B and C).
Der erste der beiden großen Blöcke
Block B erreichte am 9. März 1984 erstmals die Kritikalität und wurde am 16. März mit dem Netz synchronisiert. Der kommerzielle Leistungsbetrieb begann am 19. Juli 1984. Der Reaktor hatte 3.840 Megawatt thermische und 1.344 Megawatt elektrische Bruttoleistung. Sein Kern enthielt 784 Brennelemente. Über 33 Betriebsjahre erzeugte Block B rund 330 Milliarden Kilowattstunden Strom.
Schadsoftware an der Lademaschine
Im April 2016 wurde auf einem Service-PC der Brennelement-Lademaschine Schadsoftware entdeckt. Aufgefallen war sie, als ein Virenschutzprogramm einen zuvor mit diesem Rechner verwendeten USB-Stick prüfte. Die Untersuchung ergab weitere infizierte Datenträger. Nach Angaben des Betreibers und der bayerischen Atomaufsicht handelte es sich um gewöhnliche Büroschadsoftware, keinen nachgewiesenen gezielten Angriff. Der betroffene Rechner diente der Auswertung von Lademaschinendaten und hatte keinen Einfluss auf deren Steuerung. Sicherheitstechnisch wichtige Systeme waren nach den Untersuchungen nicht betroffen.
Rückbau bei laufendem Nachbarblock
Am 31. Dezember 2017 wurde Block B abgeschaltet. Die Stilllegungs- und Abbaugenehmigung erhielt er im März 2019. Im November 2018 und Anfang 2019 wurden teilweise abgebrannte Brennelemente von Block B nach Block C transportiert, wo sie weiterverwendet werden konnten. Seit September 2022 ist Block B vollständig brennelementfrei. Die übrigen radioaktiven Stoffe und Komponenten werden im Rahmen des Rückbaus zerlegt, behandelt oder zur späteren Entsorgung verpackt.
The first of the two large units
Unit B first achieved criticality on 9 March 1984 and was synchronised with the grid on 16 March. Commercial power operation began on 19 July 1984. The reactor had a thermal power of 3,840 megawatts and a gross electrical output of 1,344 megawatts. Its core contained 784 fuel assemblies. Over 33 years of operation, Unit B generated around 330 billion kilowatt-hours of electricity.
Malware on the fuel-loading machine's computer
In April 2016, malware was discovered on a service PC associated with the fuel-loading machine. It came to light when antivirus software scanned a USB stick previously used with that computer. The investigation found further infected storage devices. According to the operator and the Bavarian nuclear regulator, this was ordinary office malware, not a proven targeted attack. The affected computer was used to evaluate data from the loading machine and had no control over its operation. The investigations found that safety-related systems had not been affected.
Dismantling while the neighbouring unit remained in operation
Unit B was shut down on 31 December 2017. Its decommissioning and dismantling licence was issued in March 2019. In November 2018 and early 2019, partly spent fuel assemblies were transferred from Unit B to Unit C, where they could be used further. Unit B has been completely free of fuel assemblies since September 2022. The remaining radioactive materials and components are being dismantled, treated or packaged for subsequent disposal as part of the decommissioning programme.
- Reaktortyp
- Siedewasserreaktor
- Bauart / Modell
- Baulinie 72
- Hersteller
- Kraftwerk Union (KWU)
- Betreiber
- Kernkraftwerk Gundremmingen GmbH
- Leistung thermisch
- 3.840 MW
- Leistung elektrisch
- 1.344 MW brutto / 1.284 MW netto
- Brennelemente
- 784
- Baubeginn
- 20.7.1976
- Erstkritikalität
- 9.3.1984
- Netzanschluss
- 16.3.1984
- Kommerzieller Betrieb
- 19.7.1984
- Abschaltung
- 31.12.2017
- Status
- im Rückbau
- Naturzug-Nasskühlturm
Betreiber
Die beiden Blöcke B und C wurden gemeinsam von RWE und Bayernwerk getragen. Die Beteiligung des Bayernwerks ging im Zuge der Neuordnung der Stromkonzerne an E.ON und später PreussenElektra. Betreiber blieb die Kernkraftwerk Gundremmingen GmbH.
- Reactor type
- Boiling water reactor
- Design / model
- Line 72
- Manufacturer
- Kraftwerk Union (KWU)
- Operator
- Kernkraftwerk Gundremmingen GmbH
- Thermal power
- 3,840 MW
- Electrical output
- 1,344 MW gross / 1,284 MW net
- Fuel assemblies
- 784
- Construction began
- 20 July 1976
- First criticality
- 9 March 1984
- Grid connection
- 16 March 1984
- Commercial operation
- 19 July 1984
- Shutdown
- 31 December 2017
- Status
- Undergoing dismantling
- Natural-draught wet cooling tower
Operator
Units B and C were jointly backed by RWE and Bayernwerk. As the electricity groups were reorganised, Bayernwerk's shareholding passed to E.ON and later PreussenElektra. Kernkraftwerk Gundremmingen GmbH remained the operating company.
Glossar:Glossary:
Siedewasserreaktor (SWR)
Leichtwasserreaktor, in dem das Kühlwasser bei einem Druck von etwa 70 bar im Reaktorkern selbst siedet. Der entstehende Dampf wird nach der Abscheidung von Wassertröpfchen direkt zur Turbine geleitet. Anders als beim Druckwasserreaktor gibt es keinen getrennten Dampfkreislauf mit Dampferzeugern. Das Wasser dient zugleich als Kühlmittel und Moderator.
Da der Dampf unmittelbar aus dem Reaktor stammt, wird auch das Maschinenhaus in den Strahlenschutz einbezogen. Die Steuerstäbe werden von unten in den Reaktorkern eingefahren.
Die Siedewasserreaktortechnik wurde maßgeblich von General Electric in den USA entwickelt. In der Bundesrepublik baute die AEG auf Grundlage einer GE-Lizenz das Versuchsatomkraftwerk Kahl und später unter anderem Gundremmingen A, Lingen und Würgassen. Unter dem Dach der Kraftwerk Union (KWU), in der AEG und Siemens ab 1969 ihre Kraftwerksgeschäfte zusammenführten, entwickelten sich daraus die Baulinien 69 (unter anderem Brunsbüttel, Isar 1, Philippsburg 1, Krümmel und Zwentendorf) und 72 (Gundremmingen B und C).
Baulinie 72
Die KWU-Baulinie 72 war die letzte in Deutschland errichtete Generation großer Siedewasserreaktoren. Ihre beiden einzigen Anlagen Gundremmingen B und C besaßen einen zylindrischen Sicherheitsbehälter aus Spannbeton mit Stahlauskleidung statt der Stahlkugel der Baulinie 69.
Zwei Reaktoren einer neuen Generation
Die Kraftwerk Union entwickelte die Baulinie 72 als Nachfolger der Baulinie 69. Während deren Reaktoren einen kugelförmigen Sicherheitsbehälter aus Stahl besaßen, erhielten die neuen Blöcke einen zylindrischen Sicherheitsbehälter aus vorgespanntem Beton mit innenliegender Stahlauskleidung. Überströmrohre leiteten bei einem Kühlmittelverlust austretenden Dampf in die Wasservorlage der tiefliegenden Kondensationskammer, wo er kondensierte.
Die beiden in Gundremmingen errichteten Blöcke verfügten über je 784 Brennelemente, acht reaktorinterne Umwälzpumpen und eine thermische Leistung von 3.840 Megawatt.
Glossar:Glossary:
Boiling Water Reactor (BWR)
A light-water reactor in which the cooling water boils inside the reactor core at a pressure of approximately 70 bar. After water droplets have been separated out, the resulting steam passes directly to the turbine. Unlike a pressurised water reactor, it has no separate steam circuit with steam generators. The water serves as both coolant and moderator.
Because the steam comes directly from the reactor, radiation protection requirements also extend to the turbine building. Control rods are inserted into the reactor core from below.
Boiling water reactor technology was developed principally by General Electric in the United States. In West Germany, AEG built the Kahl experimental nuclear power station under a GE licence and later built Gundremmingen A, Lingen and Würgassen, among others. Within Kraftwerk Union (KWU), into which AEG and Siemens merged their power station businesses from 1969, this led to Design Generations 69 (including Brunsbüttel, Isar 1, Philippsburg 1, Krümmel and Zwentendorf) and 72 (Gundremmingen B and C).
Design Generation 72
KWU’s Design Generation 72 (Baulinie 72) was the last generation of large boiling water reactors built in Germany. Its only two units, Gundremmingen B and C, had cylindrical containment structures made of prestressed concrete with steel liners, rather than the steel sphere used in Generation 69.
Two Reactors of a New Generation
Kraftwerk Union developed Generation 72 as the successor to Generation 69. Whereas the earlier reactors had spherical steel containment vessels, the new units featured cylindrical prestressed-concrete containment structures with internal steel liners. In the event of a loss of coolant, overflow pipes directed escaping steam into the pool of water in the low-lying suppression chamber, where it condensed.
Each of the two units built at Gundremmingen had 784 fuel assemblies, eight internal recirculation pumps and a thermal output of 3,840 MW.
Vier Jahre allein
Am 26. Oktober 1984 erreichte Block C erstmals die Kritikalität, am 2. November wurde er mit dem Stromnetz verbunden. Der kommerzielle Leistungsbetrieb begann am 18. Januar 1985. Leistung und wesentliche technische Auslegung entsprachen dem Schwesterblock B. Insgesamt erzeugte der Reaktor rund 362 Milliarden Kilowattstunden Strom.
Nach der Abschaltung von Block B Ende 2017 blieb C noch vier Jahre allein in Betrieb. Als er am 31. Dezember 2021 vom Netz ging, endete auch der Leistungsbetrieb deutscher Siedewasserreaktoren. Am selben Tag wurden die Druckwasserreaktoren Grohnde und Brokdorf abgeschaltet. Nur noch die drei Konvoi-Anlagen Isar 2, Emsland und Neckarwestheim II blieben bis April 2023 in Betrieb.
Die letzten Brennelemente
Die Stilllegungs- und Abbaugenehmigung für Block C wurde im Mai 2021 erteilt. Nach dem Betriebsende begann im Januar 2022 der Rückbau. Stand Oktober 2026 befinden sich noch Brennelemente in Block C; ihre vollständige Entfernung ist nach Betreiberplanung bis Ende 2026 vorgesehen. Sie sollen in das Standortzwischenlager überführt werden.
Four years on its own
Unit C first achieved criticality on 26 October 1984 and was connected to the grid on 2 November. Commercial power operation began on 18 January 1985. Its output and principal design features were the same as those of its sister unit, B. The reactor generated around 362 billion kilowatt-hours of electricity in total.
Following the shutdown of Unit B at the end of 2017, Unit C remained in operation alone for another four years. When it was disconnected from the grid on 31 December 2021, electricity generation by Germany's boiling water reactors came to an end. The pressurised water reactors at Grohnde and Brokdorf were shut down on the same day. Only the three Konvoi units – Isar 2, Emsland and Neckarwestheim II – continued operating until April 2023.
The last fuel assemblies
The decommissioning and dismantling licence for Unit C was issued in May 2021. Dismantling began in January 2022 after the end of power operation. As of October 2026, fuel assemblies still remain in Unit C; under the operator's plans, their complete removal is scheduled for the end of 2026. They are to be transferred to the on-site interim storage facility.
- Reaktortyp
- Siedewasserreaktor
- Bauart / Modell
- Baulinie 72
- Hersteller
- Kraftwerk Union (KWU)
- Betreiber
- Kernkraftwerk Gundremmingen GmbH
- Leistung thermisch
- 3.840 MW
- Leistung elektrisch
- 1.344 MW brutto / 1.284 MW netto
- Brennelemente
- 784
- Baubeginn
- 20.7.1976
- Erstkritikalität
- 26.10.1984
- Netzanschluss
- 2.11.1984
- Kommerzieller Betrieb
- 18.1.1985
- Abschaltung
- 31.12.2021
- Status
- im Rückbau
- Naturzug-Nasskühlturm
Betreiber
Die Blöcke B und C wurden als Gemeinschaftskraftwerk von RWE und Bayernwerk errichtet. Die Bayernwerk-Beteiligung gelangte später über E.ON zu PreussenElektra. Die Kernkraftwerk Gundremmingen GmbH blieb die Betreibergesellschaft; eine Umorganisation des Gesellschafterkreises ist kein Betreiberwechsel.
- Reactor type
- Boiling water reactor
- Design / model
- Line 72
- Manufacturer
- Kraftwerk Union (KWU)
- Operator
- Kernkraftwerk Gundremmingen GmbH
- Thermal power
- 3,840 MW
- Electrical output
- 1,344 MW gross / 1,284 MW net
- Fuel assemblies
- 784
- Construction began
- 20 July 1976
- First criticality
- 26 October 1984
- Grid connection
- 2 November 1984
- Commercial operation
- 18 January 1985
- Shutdown
- 31 December 2021
- Status
- Undergoing dismantling
- Natural-draught wet cooling tower
Operator
Units B and C were built as a joint project by RWE and Bayernwerk. The Bayernwerk shareholding later passed through E.ON to PreussenElektra. Kernkraftwerk Gundremmingen GmbH remained the operating company; a reorganisation of shareholders does not constitute a change of operator.
Glossar:Glossary:
Siedewasserreaktor (SWR)
Leichtwasserreaktor, in dem das Kühlwasser bei einem Druck von etwa 70 bar im Reaktorkern selbst siedet. Der entstehende Dampf wird nach der Abscheidung von Wassertröpfchen direkt zur Turbine geleitet. Anders als beim Druckwasserreaktor gibt es keinen getrennten Dampfkreislauf mit Dampferzeugern. Das Wasser dient zugleich als Kühlmittel und Moderator.
Da der Dampf unmittelbar aus dem Reaktor stammt, wird auch das Maschinenhaus in den Strahlenschutz einbezogen. Die Steuerstäbe werden von unten in den Reaktorkern eingefahren.
Die Siedewasserreaktortechnik wurde maßgeblich von General Electric in den USA entwickelt. In der Bundesrepublik baute die AEG auf Grundlage einer GE-Lizenz das Versuchsatomkraftwerk Kahl und später unter anderem Gundremmingen A, Lingen und Würgassen. Unter dem Dach der Kraftwerk Union (KWU), in der AEG und Siemens ab 1969 ihre Kraftwerksgeschäfte zusammenführten, entwickelten sich daraus die Baulinien 69 (unter anderem Brunsbüttel, Isar 1, Philippsburg 1, Krümmel und Zwentendorf) und 72 (Gundremmingen B und C).
Baulinie 72
Die KWU-Baulinie 72 war die letzte in Deutschland errichtete Generation großer Siedewasserreaktoren. Ihre beiden einzigen Anlagen Gundremmingen B und C besaßen einen zylindrischen Sicherheitsbehälter aus Spannbeton mit Stahlauskleidung statt der Stahlkugel der Baulinie 69.
Zwei Reaktoren einer neuen Generation
Die Kraftwerk Union entwickelte die Baulinie 72 als Nachfolger der Baulinie 69. Während deren Reaktoren einen kugelförmigen Sicherheitsbehälter aus Stahl besaßen, erhielten die neuen Blöcke einen zylindrischen Sicherheitsbehälter aus vorgespanntem Beton mit innenliegender Stahlauskleidung. Überströmrohre leiteten bei einem Kühlmittelverlust austretenden Dampf in die Wasservorlage der tiefliegenden Kondensationskammer, wo er kondensierte.
Die beiden in Gundremmingen errichteten Blöcke verfügten über je 784 Brennelemente, acht reaktorinterne Umwälzpumpen und eine thermische Leistung von 3.840 Megawatt.
Glossar:Glossary:
Boiling Water Reactor (BWR)
A light-water reactor in which the cooling water boils inside the reactor core at a pressure of approximately 70 bar. After water droplets have been separated out, the resulting steam passes directly to the turbine. Unlike a pressurised water reactor, it has no separate steam circuit with steam generators. The water serves as both coolant and moderator.
Because the steam comes directly from the reactor, radiation protection requirements also extend to the turbine building. Control rods are inserted into the reactor core from below.
Boiling water reactor technology was developed principally by General Electric in the United States. In West Germany, AEG built the Kahl experimental nuclear power station under a GE licence and later built Gundremmingen A, Lingen and Würgassen, among others. Within Kraftwerk Union (KWU), into which AEG and Siemens merged their power station businesses from 1969, this led to Design Generations 69 (including Brunsbüttel, Isar 1, Philippsburg 1, Krümmel and Zwentendorf) and 72 (Gundremmingen B and C).
Design Generation 72
KWU’s Design Generation 72 (Baulinie 72) was the last generation of large boiling water reactors built in Germany. Its only two units, Gundremmingen B and C, had cylindrical containment structures made of prestressed concrete with steel liners, rather than the steel sphere used in Generation 69.
Two Reactors of a New Generation
Kraftwerk Union developed Generation 72 as the successor to Generation 69. Whereas the earlier reactors had spherical steel containment vessels, the new units featured cylindrical prestressed-concrete containment structures with internal steel liners. In the event of a loss of coolant, overflow pipes directed escaping steam into the pool of water in the low-lying suppression chamber, where it condensed.
Each of the two units built at Gundremmingen had 784 fuel assemblies, eight internal recirculation pumps and a thermal output of 3,840 MW.